A 110-30-11
1
  • A 110-30-11
2
views: 400

A 110-30-11

Rate:
0.0000/5

( 0 reviews )

Item NO.: abb0068 MOQ: 0
Weight:    3kgs
Package Size:  
 Price:
$219.00
 Qty:
      $219.00
 Shipping:   Calculate Shipping Cost


General Information

  • Extended Product Type:
    A110-30-11 220V 50Hz / 220-240V 60Hz
  • Product ID:
    1SFL451001R7611
  • EAN:
    7320500141625
  • Catalog Description:
    A110-30-11 220V 50Hz / 220-240V 60Hz Contactor
  • Long Description:
    A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V.Operated with control voltage, versions from 24….690 AC, 50 and 60 Hz

Ordering

  • EAN:
    7320500141625
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85364900

Dimensions

  • Product Net Width:
    102.0 mm
  • Product Net Depth:
    123.5 mm
  • Product Net Height:
    148.0 mm
  • Product Net Weight:
    2.040 kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    140 mm
  • Package Level 1 Length:
    140 mm
  • Package Level 1 Height:
    170 mm
  • Package Level 1 Gross Weight:
    2 kg
  • Package Level 1 EAN:
    7320500141625

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    1
  • Number of Auxiliary Contacts NC:
    1
  • Rated Operational Voltage:
    Main Circuit 1000 V
  • Rated Frequency (f):
    Main Circuit 50/60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 160 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 55 °C 145 A
    (690 V) 40 °C 160 A
    (690 V) 70 °C 130 A
  • Rated Operational Current AC-3 (Ie):
    (1000 V) 55 °C 30 A
    (690 V) 55 °C 82 A
    (220 / 230 / 240 V) 55 °C 110 A
    (415 V) 55 °C 110 A
    (440 V) 55 °C 100 A
    (380 / 400 V) 55 °C 110 A
    (500 V) 55 °C 100 A
  • Rated Operational Power AC-3 (Pe):
    (500 V) 59 kW
    (1000 V) 40 kW
    (690 V) 75 kW
    (220 / 230 / 240 V) 30 kW
    (380 / 400 V) 55 kW
    (440 V) 59 kW
    (415 V) 59 kW
  • Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
    8 x Ie AC-3
  • Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
    10 x Ie AC-3
  • Short-Circuit Protective Devices:
    gG Type Fuses 200 A
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 500 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 800 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 175 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1320 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 350 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A
  • Maximum Electrical Switching Frequency:
    AC-3 300 cycles per hour
    AC-1 300 cycles per hour
    AC-2 / AC-4 150 cycles per hour
  • Rated Operational Current DC-1 (Ie):
    (110 V) 2 Poles in Series, 40 °C 160 A
    (220 V) 3 Poles in Series, 40 °C 160 A
  • Rated Operational Current DC-3 (Ie):
    (110 V) 2 Poles in Series, 40 °C 160 A
    (220 V) 3 Poles in Series, 40 °C 160 A
  • Rated Operational Current DC-5 (Ie):
    (110 V) 2 Poles in Series, 40 °C 160 A
    (220 V) 3 Poles in Series, 40 °C 160 A
  • Rated Insulation Voltage (Ui):
    acc. to UL/CSA 600 V
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
  • Rated Impulse Withstand Voltage (Uimp):
    Main Circuit 8 kV
  • Mechanical Durability:
    10 million
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Coil Operating Limits:
    (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
  • Rated Control Circuit Voltage (Uc):
    60 Hz 220 … 240 V
    50 Hz 220 V
  • Coil Consumption:
    Pull-in at Max. Rated Control Circuit Voltage 60 Hz 450 V·A
    Holding at Max. Rated Control Circuit Voltage 50 Hz 22 V·A
    Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A
    Holding at Max. Rated Control Circuit Voltage 60 Hz 26 V·A
  • Operate Time:
    Between Coil Energization and NO Contact Closing 10 ... 25 ms
    Between Coil De-energization and NO Contact Opening 10 ... 18 ms
    Between Coil De-energization and NC Contact Closing 7 ... 15 ms
    Between Coil Energization and NC Contact Opening 7 ... 22 ms
  • Connecting Capacity-Main Circuit:
    Flexible with Cable End 2x6…35 mm²
    Bar 30 mm²
    Rigid 2x6…65 mm²
  • Connecting Capacity-Auxiliary Circuit:
    Solid 2x1…4 mm²
    Flexible with Insulated Ferrule 2x0.75…2.5 mm²
    Stranded 2x1…4 mm²
    Flexible 2x0.75…2.5 mm²
    Flexible with Ferrule 1x0.75…2.5 mm²
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
    acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
  • Connecting terminals (delivered in open position) Main poles:
    M8 hexagon socket screw with single connector
  • Terminal Type:
    Cable Clamp

Environmental

  • Ambient Air Temperature:
    Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
    Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
    Close to Contactor for Storage -60…+80 °C
  • Maximum Operating Altitude Permissible:
    3000 m
  • Resistance to Shock acc. to IEC 60068-2-27:
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 15 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 15 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 20 g
    Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 g



Contact Information:

 

Wechat: +86 133 5926 9377

Email:  rig123@rig123.com

Skype:  liuyongjie67

QQ: 526354062

 

If you have any questions,pls do not hesitate to contact us .

 

Attention: Please kindly leave us your phone number ,and also a full and accurate shipping address. 

 

Remark : please kindly add our email to your "white-list" or sign"important" then you can get our message successfully every time,like special offer, promotion sale ,technic info , and so on ,thanks !

 



 
No comment
Total 0 records, divided into1 pages. First Prev Next Last
View History
Business time
9:00-22:00
  • Email:support@rig123.com